If you are looking for an independently validated UV system for supplemental disinfection of a potable water source, Luminor's “NSF 55 CLASS B” validated system is your solution.
The BLACKCOMB 5.1 model is factory-ready to accept a UV sensor in the future if desired. The BLACKCOMB 6.1 model includes a true 254nm Teflon® based UV sensor to continuously monitor the UV intensity, displaying it as a percentage on the color screen.
The color screen controller has a user interface with screens displaying diagnostics, status, warnings and QR codes.
Features
• True 254nm Teflon® based UV sensor measures continuously, displaying UV intensity as a % – standard on LB6 / LBH6 units ONLY
• Color screen controller with Lightlock™ for protected lamp replacement
• Expandability port for future upgrades and options
• Axial flow, stainless steel polished reactors, designed & manufactured to ASME pressure vessel standards
• Simple lamp changes
• Reliable, industry proven, proprietary low pressure coated UV lamps with ceramic bases for durability and long life
• Constant current electronic controller in a splash proof case
• Full customization available as an option – language, home screen, phone number, QR codes, etc.
BLACKCOMB (Standard-output) | BLACKCOMB-HO (High-output, compact design) | |||||||||
Model | LB5-021B LB6-021B | LB5-031B LB6-031B | LB5-061B LB6-061B | LB5-101B LB6-101B | LB5-151B LB6-151B | LBH5-051B LBH6-051B | LBH5-101B LBH6-101B | LBH5-151B LBH6-151B | LBH5-251B LBH6-251B | LBH5-401B LBH6-401B |
NSF Class A Flow Rate (16mJ/cm2 @ 70% UVT) | 2.9 GPM | 5.2 GPM | 7.6 GPM | 13.0 GPM | 22.0 GPM | 5.4 GPM | 7.6 GPM | 13 GPM | 22 GPM | 28 GPM |
11.0 lpm | 19.7 lpm | 28.8 lpm | 49.2 lpm | 83.3 lpm | 20.4 lpm | 28.8 lpm | 49.2 lpm | 83.3 lpm | 106.0 lpm | |
0.7 m3/hr | 1.18 m3/hr | 1.73 m3/hr | 2.95 m3/hr | 5.00 m3/hr | 1.23 m3/hr | 1.73 m3/hr | 2.95 m3/hr | 5.00 m3/hr | 6.36 m3/hr | |
Flow Restrictor | Integral | |||||||||
Port Size | ½”FNPT | ½”MNPT | ¾”MNPT | ¾”MNPT | 1”MNPT | ½”MNPT | ¾”MNPT | 1”MNPT | 1”MNPT | 1 ½”MNPT |
Lamp Watts | 8 | 15 | 22 | 39 | 50 | 18 | 34 | 45 | 67 | 101 |
Power (Watts) | 14 | 20 | 30 | 49 | 62 | 20 (19 @ 230V.) | 38 (36 @ 230V.) | 57 (48 @ 230V.) | 73 (72 @ 230V.) | 115 (108 @ 230V.) |
Maximum Current (amps) | 1 | |||||||||
Replacement Lamp | RL-210 | RL-920 | RL-470 | RL-820 | RL-999 | RL-210HO | RL-330HO | RL-420HO | RL-600HO | RL-950HO |
Replacement Sleeve | RQ-210 | RQ-290 | RQ-470 | RQ-820 | RQ-999 | RQ-210 | RQ-330 | RQ-420 | RQ-600 | RQ-950 |
Replacement UV Sensor | RS-B2.5 | RSHO-B3.5 | ||||||||
Chamber Material | Polished 304 stainless steel, A249 pressure rated tubing | Polished 316L stainless steel, A249 pressure rated tubing | ||||||||
Operating Pressure | 0.7-10.3 bar (10-150 psi) | |||||||||
Operating Water Temp. | 2-40° C (36 - 104°F) | |||||||||
UV Monitor | YES on all LB6 / LBH6 units , OPTIONAL on all LB5 / LBH5 units (RS-2.5 for LB5/6 units and RSHO.3.5 for LBH5/6 units) | |||||||||
Solenoid Output | YES (but requires optional solenoid module (MOD-SOL) | |||||||||
Dry Contacts | YES (but requires optional remote alarm module (Dry Contacts) (MOD-RAM) | |||||||||
4-20 mA Output | YES (but requires optional 4-20mA module (MOD-420) | |||||||||
Lamp Change Reminder | YES (both audible and visual (full color graphic)) | |||||||||
Lamp Out Indicator | YES (both audible and visual (full color graphic)) | |||||||||
Shipping Weight | 6.6 lbs | 7.3 lbs | 9.3 lbs | 15.0 lbs | 17.6 lbs | 9.9 lbs | 11.9 lbs | 13.2 lbs | 16.1 lbs | 21.6 lbs |